Areas of Use

These screened cables are used as signal transmission cables for indoor applications. These can be easily used with their flexible construction in narrow applications like electronic control systems of computer or audio systems or communication sector, electronic circuits, measurement devices, machine design, office equipment, etc. Screening protects the cable from the outer electrical effects. These cables have HFFR material in their construction and These don't burn easily and if these do the flames go off by themselves. These have low smoke density and These don't emit poisonous and corrosive gases during the fire. These used in buildings where there are important goods or human population.

Cable Construction

  • Conductor Stranded Annealed Copper (IEC/EN 60228, Class 5, 0.34 mm²: Class 2)
  • Insulation HFFR (EN 50290-2-26)
  • Core Colors DIN 47100 (4 cores colors, white, yellow, brown, green)
  • Lay-up Cores are stranded in layers
  • Separator PET Foil
  • Screen Tinned Copper Wire Braid
  • Outer Sheath HFFR (EN 50290-2-27), RAL 7001 - Grey
  • Reference Standards VDE 0812, TS 13755
  • CPR Classes B2ca s1a d1 a1

Technical Properties

  • Operating Voltage 0.14 mm²..0.25 mm² 250 V; 0.34 mm²..1.50 mm² 300 V / 500 V; 2.50 mm²…... 450 V / 750 V
  • Test Voltage 0.14 mm² - 800 V; 0.22 mm² ….1.00 mm²- 1200 V; 1.50 mm²….. 2.50 mm² - 2500 V
  • Conductor Resistance 0.14 mm²- ≤138 Ω/km; 0.22 mm²- ≤85 Ω/km; 0.25 mm²- ≤77.8 Ω/km; 0.34 mm²- ≤56 Ω/km; 0.50 mm²- ≤39 Ω/km; 0.75 mm²- ≤26Ω/km; 1.00 mm²- ≤19.5 Ω/km; 1.50 mm²- ≤13.3 Ω/km; 2.50 mm²- ≤7.98 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Capacitance (@800Hz) Core - Core: 0.14 mm²-≤80 nF/km; 0.22 mm²..0.34 mm²-≤100 nF/km; 0.50 mm²..0.75 mm²-≤110 nF/km; 1.00 mm²..1.50 mm²-≤120nF/km; 2.50 mm²- ≤140 nF/km Core-Screen: 0.14 mm²-≤120 nF/km; 0.22 mm²..0.34 mm²-≤150 nF/km; 0.50 mm²..0.75 mm²-≤170 nF/km; 1.00 mm²..1.50 mm²-≤180nF/km; 2.50 mm²- ≤240 nF/km
  • Indutance (approx.) 0.65 mH/km
  • Temperature Range Fixed: -30 °C ........+70 °C, Flexible: -5 °C ........+70 °C
  • Flame Retardancy IEC/EN 60332-1
  • Smoke Density IEC/EN 61034-2
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Min. Bending Radius Fixed: 8 x Cable Diameter, Flexible: 15 x Cable Diameter