ÜRÜNLER
- Yangına Dayanıklı Kablolar
TYPE ITC/PLTC-ER - Overall Shielded Pairs (Triads) Braid Armored
Instrumentation cables have a wide range of usage in process control and data processes, in analog and digital signal transmission. Factories, refineries, petrochemical plants, power plants, natural gas filling plants etc. make up the general areas that these cables are used. These cables meets the crush and impact requirements and deformation resistance according to UL 2556.
- Conductor Stranded Annealed Copper (ASTM B3)
- Insulation PVC (UL 1581 Class 105°C, EN 50363‐3 TI3)
- Core Colors Pair: Black / White, Numbered Triples: Black / White / Red, Numbered Quad: Black / White / Red / Blue, Numbered
- Lay-up Pairs / triples / quads are stranded in layers
- Separator PET Foil
- Overall Screen Al-PET Foil (with 7x0.3 mm Tinned Copper Drain Wire)
- Inner Sheath PVC (UL 1581 Class 105°C)
- Armour Galvanised Steel Wire Braid
- Outer Sheath Heat Resistant and Sunlight Resistant PVC (UL 1581 Class 105°C), Black, Blue (other colors upon request)
- Reference Standards UL 13, UL 2250, NEC Article 725, NEC Article 727
- Operating Voltage 300 V
- Test Voltage 1.5 kV
- Dielectric Voltage Withstand UL 2556
- Conductor Resistance UL 1581 - Section 220
- Insulation Resistance >100.1 MΩ/kft (at 15.6°C)
- Max. Operating Temperature Fixed: -40°C … +105°C, Flexible: -5°C … +60°C
- Flame Retardancy FT4/IEEE 1202 Flame Test (UL 1685), IEC/EN 60332-1, IEC/EN 60332-3-24 (CAT C)
- Oil Resistance ASTM No 2 oil 70°C 4 hours (IEC / EN 60811- 404)
- Sunlight Resistance Acc. to UL 1581, Sec. 1200
- Min. Bending Radius (Fixed) 8 x Cable Diameter