PT1 T2

  • Long-Lasting Use

  • Trouble-Free Operation

  • Effective and Profitable

  • Flexible and Convenient

Instrumentation cables have a wide range of usage in process control and data processes, in analog and digital signal transmission. Factories, refineries, petrochemical plants, power plants, natural gas filling plants, etc. make up the general areas that these cables are used.

  • Conductor Solid or Stranded Annealed Copper (IEC/EN 60228, Class 1, 2,5) -Table 1
  • Insulation PE (EN 50290-2-23)
  • Core Colors According to PAS 5308-1 Annex C-Table 2
  • Lay-up Cores / pairs / triples are stranded in layers, Two-pair cables laid in quad formation
  • Separator PET Foil
  • Overall Screen Al-PET Foil (with 7x0.3 mm Tinned Copper Drain Wire)
  • Inner Sheath PE
  • Armour Round Galvanized Steel Wire (Min. Diameter 0.90 mm ±0.02 mm)
  • Outer Sheath UV Resistant, Flame Retardant PVC (EN 50290-2-22 ), RAL 9005 - Black, RAL 5015 - Blue (other colors upon request)
  • Reference Standards PAS 5308 Part 1 - Type 2
  • Operating Voltage 300 V / 500 V
  • Test Voltage Core - Core: 2000 V; Core - Screen: 1000 V
  • Conductor Resistance 0.50 mm² - ≤36.8 Ω/km; 0.75 mm² - ≤24.5 Ω/km; 1.00 mm² - ≤18.4 Ω/km; 1.50 mm² - ≤12.3 Ω/km; 2.50 mm² - ≤7.6 Ω/km
  • Insulation Resistance >5000 M.Ωxkm
  • Capacitance Unbalance (800 Hz) ≤500 pF/500m
  • Capacitance (@800Hz) Table-3
  • L/R Ratio 0.50 mm²..1.00 mm² - ≤25 µH/Ω; 1.30 mm²..1.50 mm² - ≤40 µH/Ω; 2.50 mm² - ≤60 µH/Ω
  • Temperature Range Fixed: -40 °C ........+70 °C, Flexible: -5 °C ........+50 °C
  • Flame Retardancy IEC/EN 60332-1, IEC/EN 60332-3-24 (CAT C)
  • Oil Resistance IEC/EN 60811-404, ASTM No 2 oil 70 °C 4 hours
  • Min. Bending Radius (Fixed) 12 x Cable Diameter