PT1 T1 ICAT LSZH

  • Long-Lasting Use

  • Trouble-Free Operation

  • Effective and Profitable

  • Flexible and Convenient

Instrumentation cables have a wide range of usage in process control and data processes, in analog and digital signal transmission. Factories, refineries, petrochemical plants, power plants, natural gas filling plants, etc. make up the general areas that these cables are used.

  • Conductor Solid or Stranded Annealed Copper (IEC/EN 60228, Class 1, 2,5) -Table 1
  • Insulation PE (EN 50290-2-23)
  • Core Colors According to PAS 5308-1 Annex C-Table 2
  • Separator PET Foil
  • Individual Screen Al-PET Foil (with 7x0.30 mm Tinned Copper Drain Wire)
  • Lay-up Shielded pairs are stranded in layers
  • Separator PET Foil
  • Overall Screen Al-PET Foil (with 7x0.3 mm Tinned Copper Drain Wire)
  • Outer Sheath Halogen Free Flame Retardant Compound (HFFR /LSZH/LSOH/FRNC) (EN 50290-2-27), RAL 9005 - Black, RAL 5015 - Blue (other colors upon request)
  • Operating Voltage 300 V / 500 V
  • Test Voltage Core - Core: 2000 V; Core - Screen: 1000 V
  • Conductor Resistance 0.50 mm² - ≤36.8 Ω/km; 0.75 mm² - ≤24.5 Ω/km; 1.00 mm² - ≤18.4 Ω/km; 1.50 mm² - ≤12.3 Ω/km; 2.50 mm² - ≤7.6 Ω/km
  • Insulation Resistance >5000 M.Ωxkm
  • Capacitance Unbalance (800 Hz) ≤500 pF/500m
  • Capacitance (@800Hz) Table-3
  • L/R Ratio 0.50 mm²..1.00 mm² - ≤25 µH/Ω; 1.30 mm²..1.50 mm² - ≤40 µH/Ω; 2.50 mm² - ≤60 µH/Ω
  • Temperature Range Fixed: -40 °C ........+70 °C, Flexible: -5 °C ........+50 °C
  • Flame Retardancy IEC/EN 60332-1, IEC/EN 60332-3-24 (CAT C)
  • Smoke Density IEC/EN 61034-1
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Oil Resistance IEC/EN 60811-404, ASTM No 2 oil 70 °C 4 hours
  • Min. Bending Radius (Fixed) 8 x Cable Diameter