CABLE REQUEST FORM
CABLE REQUEST FORM
PRODUCTS

FireKab LIHH FE180 PH120

SHARE

Product Certificates

You can click to download our certificates.

Areas of Use

FireKab fire resistant cables are used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, etc. FireKab products have low smoke density, are halogen-free and they don't emit poisonous gases.

Cable Construction

  • Conductor Stranded Annealed Copper (IEC/EN 60228, Class 5, 0.34 mm²: Class 2)
  • Insulation Fire Resistant Silicon Rubber (EN 50363-1, BS 7655 EI2)
  • Core Colors DIN 47100 (4 cores colors, white, yellow, brown, green, for more than 5 cores white core-black numbered)
  • Lay-up Cores are stranded in layers
  • Flame Barrier Fiber Glass Tape
  • Outer Sheath HFFR (EN 50290-2-27), RAL 2004 - Orange (other colors upon request)
  • Reference Standards TS 13734

Technical Properties

  • Operating Voltage 300 V / 500 V
  • Test Voltage 2000 V
  • Conductor Resistance 0.50 mm² - ≤39 Ω/km; 0.75 mm² - ≤26 Ω/km; 1.00 mm² - ≤19.5 Ω/km; 1.50 mm² - ≤13.3 Ω/km; 2.50 mm² - ≤7.98 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Temperature Range -30 °C........+70 °C, Flexible: -5 °C ........+60 °C
  • Flame Retardancy IEC/EN 60332-1, IEC/EN 60332-3-24
  • Fire Resistance IEC 60331-21, EN 50200 PH120
  • Smoke Density IEC/EN 61034-2
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Min. Bending Radius Fixed: 7.5 x Cable Diameter, Flexible: 15 x Cable Diameter