LIHH

SHARE

Product Certificates

You can click to download our certificates.

Areas of Use

LIHH cables are used in the industrial applications for indoor use for signal transmission. These can be easily used with their flexible construction in narrow applications like electronic control systems of computer or audio systems or the communication sector, electronic circuits, measurement devices, machine design, office equipment, etc.LIHH cables have HFFR material in their construction and These don't burn easily and the flames go off by themselves. These have low smoke density and these don't emit poisonous and corrosive gases during the fire. These used in buildings where there are important goods or human population.

Cable Construction

  • Conductor Stranded Annealed Copper (IEC/EN 60228, Class 5, 0.34 mm²: Class 2)
  • Insulation HFFR (EN 50290-2-26)
  • Core Colors DIN 47100
  • Lay-up Cores are stranded in layers
  • Outer Sheath HFFR (EN 50290-2-27), RAL 7001 - Grey
  • Reference Standards VDE 0812, TS 13755

Technical Properties

  • Operating Voltage 0.14 mm²..0.25 mm² 250 V; 0.34 mm²..1.50 mm² 300 V / 500 V; 2.50 mm²…... 450 V / 750 V
  • Test Voltage 0.14 mm²..25 mm² 1200 V; 0.34 mm²..10 mm² 1500 V; 1.50 mm²….. 2500 V
  • Conductor Resistance 0.14 mm²- ≤138 Ω/km; 0.22 mm²- ≤85 Ω/km; 0.25 mm²- ≤77.8 Ω/km; 0.34 mm²- ≤56 Ω/km; 0.50 mm²- ≤39 Ω/km; 0.75 mm²- ≤26Ω/km; 1.00 mm²- ≤19.5 Ω/km; 1.50 mm²- ≤13.3 Ω/km; 2.50 mm²- ≤7.98 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Capacitance (@800Hz) Core - Core: 0.14 mm²-≤80 nF/km; 0.22 mm²..0.34 mm²-≤100 nF/km; 0.50 mm²..0.75 mm²-≤110 nF/km; 1.00 mm²..1.50 mm²-≤120nF/km; 2.50 mm²- ≤140 nF/km
  • Indutance (approx.) 0.65 mH/km
  • Temperature Range Fixed: -30 °C ........+70 °C, Flexible: -5 °C ........+70 °C
  • Flame Retardancy IEC/EN 60332-1
  • Smoke Density IEC/EN 61034-2
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Min. Bending Radius Fixed: 8 x Cable Diameter, Flexible: 15 x Cable Diameter

Cross Section

  • Configuration / Cross-Section (mm/mm²) Cable Diameter (mm) (± 5%) Copper Weight (kg / km) ~ Cable Weight (kg / km)
  • 2x0.22 3.3 4 15
  • 3x0.22 3.4 6 18
  • 4x0.22 3.8 8 24
  • 5x0.22 4.2 11 30
  • 7x0.22 4.6 15 38
  • 9x0.22 5.5 19 51
  • 10x0.22 6.0 21 56
  • 14x0.22 6.5 29 74
  • 16x0.22 7.0 34 84
  • 20x0.22 7.8 42 102
  • 25x0.22 8.8 53 129
  • 2x0.25 3.5 5 16
  • 3x0.25 3.6 7 20
  • 4x0.25 4.0 9 26
  • 5x0.25 4.4 12 33
  • 7x0.25 4.8 17 41
  • 9x0.25 5.7 21 55
  • 10x0.25 6.3 24 60
  • 14x0.25 6.9 33 82
  • 16x0.25 7.3 38 91
  • 20x0.25 8.2 47 113
  • 25x0.25 9.2 59 140
  • 2x0.34 3.6 7 19
  • 3x0.34 3.9 10 25
  • 4x0.34 4.2 13 30
  • 5x0.34 4.7 16 40
  • 7x0.34 5.1 23 49
  • 9x0.34 6.1 30 68
  • 10x0.34 6.7 33 75
  • 14x0.34 7.4 46 101
  • 16x0.34 7.8 53 113
  • 20x0.34 8.7 66 137
  • 25x0.34 9.8 82 172
  • 2x0.5 4.4 9 27
  • 3x0.5 4.7 13 34
  • 4x0.5 5.2 17 44
  • 5x0.5 5.7 22 57
  • 7x0.5 6.3 30 71
  • 9x0.5 7.6 39 98
  • 10x0.5 8.3 43 106
  • 14x0.5 9.1 61 145
  • 16x0.5 9.7 70 164
  • 20x0.5 10.8 87 198
  • 25x0.5 12.3 109 251
  • 2x0.75 5.0 13 35
  • 3x0.75 5.3 20 46
  • 4x0.75 5.8 26 57
  • 5x0.75 6.5 33 76
  • 7x0.75 7.2 46 95
  • 9x0.75 8.6 59 130
  • 10x0.75 9.4 65 141
  • 14x0.75 10.4 91 196
  • 16x0.75 11.1 104 222
  • 18x0.75 11.7 117 244
  • 20x0.75 12.5 130 271
  • 25x0.75 13.9 163 333
  • 2x1 5.4 17 43
  • 3x1 5.6 26 54
  • 4x1 6.2 35 70
  • 5x1 6.9 43 92
  • 7x1 7.7 61 116
  • 9x1 9.1 78 158
  • 10x1 10.0 87 171
  • 14x1 11.1 122 237
  • 16x1 11.8 139 269
  • 18x1 12.5 156 296
  • 20x1 13.2 174 329
  • 25x1 14.8 217 404
  • 2x1.5 6.4 26 61
  • 3x1.5 6.8 39 81
  • 4x1.5 7.6 52 104
  • 5x1.5 8.4 65 137
  • 7x1.5 9.3 91 171
  • 9x1.5 11.1 117 235
  • 10x1.5 12.3 130 259
  • 14x1.5 13.5 182 352
  • 16x1.5 14.3 208 398
  • 20x1.5 15.9 260 479
  • 25x1.5 17.9 325 596
  • 2x2.5 7.5 43 89
  • 3x2.5 7.9 65 117
  • 4x2.5 8.9 87 154
  • 5x2.5 9.8 108 201