CABLE REQUEST FORM
CABLE REQUEST FORM
PRODUCTS

FireKab SFR FE180 PH120 Annex E

SHARE

Areas of Use

FireKab fire resistant cables are used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, etc. FireKab products have low smoke density, are halogen-free and they don't emit poisonous gases.

Cable Construction

  • Conductor Annealed Solid Copper (IEC/EN 60228 Class 1)
  • Insulation Fire Resistant Silicon Rubber (BS 7655 EI2)
  • Core Colors BS 7671 / HD308 S2
  • Lay-up Cores are stranded in layers
  • Separator PET Foil
  • Drain Wire Solid tinned copper with the same of conductor
  • Screen Al-PET Foil
  • Outer Sheath Halogen Free Flame Retardant Compound (HFFR / LSZH / LSOH / FRNC, BS 7655-6 LTS3), RAL 3000 - Red or RAL 9003 - White
  • Reference Standards BS 7629 - 1:2008

Technical Properties

  • Operating Voltage 300 V / 500 V
  • Test Voltage 2000 V
  • Conductor Resistance 1.00 mm² - ≤18 Ω/km; 1.50 mm² - ≤12 Ω/km; 2.50 mm² - ≤7.4 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Temperature Range Fixed: -30 °C........+90 °C, Flexible: -5 °C ........+60 °C
  • Flame Retardancy IEC/EN 60332-1, IEC/EN 60332-3-24
  • Fire Resistance IEC 60331-21, BS 6387 C,W,Z, EN 50200 PH120, EN Annex E (30 min.)
  • Smoke Density IEC 61034-1/2
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Min. Bending Radius Fixed: 8 x Cable Diameter, Flexible: 15 x Cable Diameter