FireKab JE-H(St)H…Bd FE180 PH120

SHARE

Product Certificates

You can click to download our certificates.

Areas of Use

FireKab fire resistant cables are used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, etc. FireKab products have low smoke density, are halogen-free and they don't emit poisonous gases.

Cable Construction

  • Conductor Annealed Solid Copper (IEC/EN 60228)
  • Insulation Fire Resistant Silicon Rubber (EN 50363-1, BS 7655 EI2)
  • Core Colors Blue/Red, Grey/Yellow, Green/Brown, White/Black - VDE 0815
  • Lay-up 4 pairs laid up to a bundle, bundles idendified by spiral numbered or colored polyester tape, bundles laid up in layers. (Two pairs laid up as a star quad)
  • Separator PET Foil
  • Flame Barrier Fiber Glass Tape
  • Drain Wire 0.80 mm Solid Tinned Copper
  • Screen Al-PET Foil
  • Outer Sheath HFFR (EN 50290-2-27), RAL 2004 - Orange (other colors upon request)

Technical Properties

  • Operating Voltage 300 V
  • Test Voltage Core - Core 500 V; Core - Screen 2000 V
  • Conductor Resistance 0.80mm - ≤36.6 Ω/km; 1.00 mm - ≤22.2 Ω/km; 1.50 mm² - ≤12.1 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Capacitance Unbalance (800 Hz) ≤200 pF/100m
  • Capacitance (@800Hz) ≤120 nF/km
  • Temperature Range Fixed: -30 °C........+90 °C, Flexible: -5 °C ........+60 °C
  • Flame Retardancy IEC/EN 60332-1, IEC/EN 60332-3-24
  • Fire Resistance IEC 60331-21, EN 50200 PH120
  • Smoke Density IEC/EN 61034-2
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Min. Bending Radius Fixed: 7.5 x Cable Diameter, Flexible: 15 x Cable Diameter