2MKAB NGF FE180 PH30
Fire-resistant cables are used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, etc. Fire-resistant products have low smoke density, are halogen-free and they don't emit poisonous gases.
- Conductor Annealed Solid Copper (IEC/EN 60228 Class 1)
- Insulation Fire Resistant Silicon Rubber (BS 7655 EI2)
- Core Colors BS 7671 / HD308 S2
- Lay-up Cores are stranded in layers
- Separator PET Foil
- Drain Wire 0.80 mm Solid Tinned Copper
- Screen Al-PET Foil
- Outer Sheath Halogen Free Flame Retardant Compound (HFFR / LSZH / LSOH / FRNC, BS 7655-6 LTS3), RAL 3000 - Red or RAL 9003 - White
- Operating Voltage 300 V / 500 V
- Test Voltage 2000 V
- Conductor Resistance 1.50 mm² - ≤12 Ω/km; 2.50 mm² - ≤7.4 Ω/km
- Insulation Resistance >200 M.Ωxkm
- Temperature Range Fixed: -30 °C........+90 °C, Flexible: -5 °C ........+60 °C
- Flame Retardancy IEC/EN 60332-1, IEC/EN 60332-3-24
- Fire Resistance IEC 60331-21, BS 6387 C,W,Z, EN 50200 PH30
- Smoke Density IEC 61034-1/2
- Amount of Halogen Acid Gas IEC/EN 60754-1
- Corrosive Gases Measurement IEC/EN 60754-2
- Min. Bending Radius Fixed: 8 x Cable Diameter, Flexible: 15 x Cable Diameter