CABLE REQUEST FORM
CABLE REQUEST FORM
PRODUCTS

YSLYSY / YSLYQY

SHARE

Areas of Use

These PVC cables (armored) are used in office equipment, electronic control systems, air condition systems, power stations, engineering projects for control, vision, and measurement purposes. These can be used in wet or dry indoor applications. Armor; protect against mechanical traverse loads and act as a magnetic screen against interference.

Cable Construction

  • Conductor Stranded Annealed Copper (IEC/EN 60228, Class 5)
  • Insulation PVC (EN 50290-2-21, TSE K 373)
  • Core Colors Black (white numbered) Green-Yellow earth core in the outer layer (3 cores and above)
  • Lay-up Cores are stranded in layers
  • Inner Sheath PVC (EN 50290-2-22, EN 50363-4-1)
  • Armour Galvanised Steel Wire Braid
  • Outer Sheath PVC (EN 50290-2-22, EN 50363-4-1), Transparent, RAL 7001 - Grey (other colors upon request)
  • Reference Standards With reference to VDE 0245

Technical Properties

  • Operating Voltage 0.50 mm²..1.50 mm² 300 V / 500 V; 2.50 mm²…... 450 V / 750 V
  • Test Voltage 2500 V
  • Conductor Resistance 0.14 mm²- ≤138 Ω/km; 0.22 mm²- ≤85 Ω/km; 0.25 mm²- ≤77.8 Ω/km; 0.34 mm²- ≤56 Ω/km; 0.50 mm²- ≤39 Ω/km; 0.75 mm²- ≤26Ω/km; 1.00 mm²- ≤19.5 Ω/km; 1.50 mm²- ≤13.3 Ω/km; 2.50 mm²- ≤7.98 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Temperature Range Fixed: -30 °C ........+70 °C, Flexible: -5 °C ........+70 °C
  • Flame Retardancy IEC/EN 60332-1
  • Min. Bending Radius Fixed: 10 x Cable Diameter, Flexible: 15 x Cable Diameter

Footnote

Depending on the customer's request, the coverage rate and voltage can be adjusted.