YSLY-JZ

SHARE

Product Certificates

You can click to download our certificates.

Areas of Use

These types of cables are used in office equipment, electronic control systems, air condition systems, power stations, engineering projects for control, vision and measurement purposes. These can be used in wet or dry indoor applications but for outdoor use, UV protected PVC must be used where the cable is exposed to sunlight.

Cable Construction

  • Conductor Stranded Annealed Copper (IEC/EN 60228, Class 5)
  • Insulation PVC (EN 50290-2-21, TSE K 373)
  • Core Colors Black (white numbered) Green-Yellow earth core in the outer layer (3 cores and above)
  • Lay-up Cores are stranded in layers
  • Outer Sheath PVC (EN 50290-2-22, EN 50363-4-1), RAL 7001 - Grey
  • Reference Standards TSE K 373

Technical Properties

  • Operating Voltage 0.50 mm²..1.50 mm² 300 V / 500 V; 2.50 mm²…... 450 V / 750 V
  • Test Voltage 2500 V
  • Conductor Resistance 0.50 mm²- ≤39 Ω/km; 0.75 mm²- ≤26 Ω/km; 1.00 mm²- ≤19.5 Ω/km; 1.50 mm²- ≤13.3 Ω/km; 2.50 mm²- ≤7.98 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Temperature Range Fixed: -30 °C ........+70 °C, Flexible: -5 °C ........+70 °C
  • Flame Retardancy IEC/EN 60332-1
  • Min. Bending Radius Fixed: 8 x Cable Diameter, Flexible: 15 x Cable Diameter