CABLE REQUEST FORM
CABLE REQUEST FORM
PRODUCTS

HSLH-JZ

SHARE

Areas of Use

These types of HFFR cables are used in office equipment, electronic control systems, air condition systems, power stations, engineering projects for control, vision and measurement purposes. These can be used in wet or dry indoor applications. Because of the HFFR material, These don't burn easily and when These do, the flames go off by themselves. These have low smoke density and These don't emit poisonous and corrosive gases during a fire. These used in buildings where there are important goods or human population.

Cable Construction

  • Conductor Stranded Annealed Copper (IEC/EN 60228, Class 5)
  • Insulation HFFR (EN 50290-2-26)
  • Core Colors Black (white numbered) Green-Yellow earth core in the outer layer (3 cores and above)
  • Lay-up Cores are stranded in layers
  • Outer Sheath HFFR (EN 50290-2-27), RAL 7001 - Grey
  • Reference Standards TS 13734

Technical Properties

  • Operating Voltage 0.50 mm²..1.50 mm² 300 V / 500 V; 2.50 mm²…... 450 V / 750 V
  • Test Voltage 2500 V
  • Conductor Resistance 0.50 mm² - ≤39 Ω/km; 0.75 mm² - ≤26 Ω/km; 1.00 mm² - ≤19.5 Ω/km; 1.50 mm² - ≤13.3 Ω/km; 2.50 mm² - ≤7.98 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Temperature Range Fixed: -30 °C ........+70 °C, Flexible: -5 °C ........+70 °C
  • Smoke Density IEC/EN 61034-2
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Min. Bending Radius Fixed: 8 x Cable Diameter, Flexible: 15 x Cable Diameter