FireKab NGF FE180 PH30

SHARE

Product Certificates

You can click to download our certificates.

Areas of Use

Fire-resistant cables are used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, etc. FireKab products have low smoke density, are halogen-free and they don't emit poisonous gases.

Cable Construction

  • Conductor Annealed Solid Copper (IEC/EN 60228 Class 1)
  • Insulation Fire Resistant Silicon Rubber (BS 7655 EI2)
  • Core Colors BS 7671 / HD308 S2
  • Lay-up Cores are stranded in layers
  • Separator PET Foil
  • Drain Wire 0.80 mm Solid Tinned Copper
  • Screen Al-PET Foil
  • Outer Sheath Halogen Free Flame Retardant Compound (HFFR / LSZH / LSOH / FRNC, BS 7655-6 LTS3), RAL 3000 - Red or RAL 9003 - White

Technical Properties

  • Operating Voltage 300 V / 500 V
  • Test Voltage 2000 V
  • Conductor Resistance 1.50 mm² - ≤12 Ω/km; 2.50 mm² - ≤7.4 Ω/km
  • Insulation Resistance >200 M.Ωxkm
  • Temperature Range Fixed: -30 °C........+90 °C, Flexible: -5 °C ........+60 °C
  • Flame Retardancy IEC/EN 60332-1, IEC/EN 60332-3-24
  • Fire Resistance IEC 60331-21, BS 6387 C,W,Z, EN 50200 PH30
  • Smoke Density IEC 61034-1/2
  • Amount of Halogen Acid Gas IEC/EN 60754-1
  • Corrosive Gases Measurement IEC/EN 60754-2
  • Min. Bending Radius Fixed: 8 x Cable Diameter, Flexible: 15 x Cable Diameter

Cross Section

  • Configuration / Cross-Section (mm/mm²) Cable Diameter (mm) (± 5%) Copper Weight (kg / km) ~ Cable Weight (kg / km)
  • 2x1.50 6.7 31 67
  • 3x1.50 7.1 43 85
  • 4x1.50 7.9 56 109
  • 2x2.50 7.9 49 96
  • 3x2.50 8.5 70 128
  • 4x2.50 9.2 93 160